Products & Services > Clean Room > Tate  
 
Products & Services
 
Floating Floors Panel Selections


Solid Panel

 
Die cast aluminum panels meet class A fire rating
 
Contains no ferrous materials to disrupt magnetic fields
 
Conductive gasket ensures continuons conductivity
 
Excellecnt rolling load performance
 
Light weight for ease of handling
 
Choice of panel cpatings: bare, E-coat, Epoxy powder coat, metalic finishes
 
   
Perforated Panel

 
Perforated panels provide optimum laminar airflow without turbulence
 
Optional chamfered perforations provide superior particulate control with up to 20% increase in airflow
 
Downward airflow performance
 
Several perforated panel patterns from which to choose
 
   
Grates

 
Designed to provide superior airflow
 
Unique octagonal design reduces rolling load vibrations
 
Fully interchangeable with FF1250 and FF3000 panels
 
A damper can be used to regulate airflow
 
Downward airflow performance
 


Floating Floors by Tate 3000 Performance Selection

Systems Type
System Weight
Static Loads (note 1)
Rolling Loads (note 2)
Impact Loads
Panel Understructure   Concentrated Loads (note 3) Top Surface Deflection Uniform Load Ultimate Load 10 Passes 10,000 Passes  
Solid Panels Stringerless
Cornerlock
7.3 lbs./ft²
35.6 kg/m²
3000 lbs.
1361 kg
.100 inch
2.54 mm

750 lbs./ft²
36 kPa

4500 lbs
2041 kg
2000 lbs
907 kg
2000 lbs
907 kg
200 lbs
90.7 kg
Bolted
Stringer
7.6 lbs./ft²
37.1 kg/m²
3000 lbs.
1361 kg
.100 inch
2.54 mm
750 lbs./ft²
36 kPa
4500 lbs
2041 kg
2000 lbs
907 kg
2000 lbs
907 kg
200 lbs
90.7 kg
Perforated Panels Stringerless
Cornerlock
7.1 lbs./ft²
34.7 kg/m²
3000 lbs.
1361 kg
.100 inch
2.54 mm
750 lbs./ft²
36 kPa
4500 lbs
1814 kg
2000 lbs
680 kg
2000 lbs
907 kg
100 lbs
45.0 kg
Bolted
Stringer
7.4 lbs./ft²
36.1 kg/m²
3000 lbs.
1361 kg
.100 inch
2.54 mm
750 lbs./ft²
36 kPa
4500 lbs
1814 kg
2000 lbs
680 kg
2000 lbs
907 kg
100 lbs
45.4 kg


Notes:

1. Loads to be applied anywhere on panel; permanent set after application of concentrated load shall be 0.010" or less.
2.
Local and beam top surface deformation shall not exceed 0.040". 10 pass test uses a 3" dia. x 1 13/16" wide phenolic wheel, 10,000 pass test uses an 8" dia. x 5" wide alathane wheel.
3. Loads applied on a one square inch area. Results above indicate weakest point of panel.
4. Tate Access Floors, Inc. Uses "Ceilings and Interior System Construction Association" (CISCA) as a guide in development of all test procedures.



Floating Floors by Tate 1250 Performance Selection

Systems Type
System Weight
Static Loads (note 1)
Rolling Loads (note 2)
Impact Loads
Panel Understructure   Concentrated Loads (note 3) Top Surface Deflection Uniform Load Ultimate Load 10 Passes 10,000 Passes  
Solid Panels Stringerless
Cornerlock
6.2 lbs./ft²
30.3 kg/m²
1250 lbs.
567 kg
.100 inch
2.54 mm

375 lbs./ft²
17.9 kPa

2500 lbs
1134 kg
1000 lbs
454 kg
1000 lbs
454 kg
150 lbs
68 kg
Bolted
Stringer
6.5 lbs./ft²
31.7 kg/m²
1250 lbs.
567 kg
.100 inch
2.54 mm
375 lbs./ft²
17.9 kPa
2500 lbs
1134 kg
1000 lbs
454 kg
1000 lbs
454 kg
150 lbs
68 kg
Perforated Panels Stringerless
Cornerlock
5.95 lbs./ft²
29.0 kg/m²
1250 lbs.
567 kg
.100 inch
2.54 mm
375 lbs./ft²
17.9 kPa
2500 lbs
1134 kg
1000 lbs
454 kg
1000 lbs
454 kg
150 lbs
68 kg
Bolted
Stringer
6.25 lbs./ft²
30.5 kg/m²
1250 lbs.
567 kg
.100 inch
2.54 mm
375 lbs./ft²
17.9 kPa
2500 lbs
1134 kg
1000 lbs
454 kg
1000 lbs
454 kg
150 lbs
68 kg
Grate Panels Stringerless
Cornerlock
6.95 lbs./ft²
33.9 kg/m²
1250 lbs.
567 kg
.100 inch
2.54 mm
375 lbs./ft²
17.9 kPa
2500 lbs
1134 kg
1000 lbs
454 kg
1000 lbs
454 kg
150 lbs
68 kg
Bolted
Stringer
7.25 lbs./ft²
35.4 kg/m²
1250 lbs.
567 kg
.100 inch
2.54 mm
375 lbs./ft²
17.9 kPa
2500 lbs
1134 kg
1000 lbs
454 kg
1000 lbs
454 kg
150 lbs
68 kg

 

 
Bolted Stringer System
 
Stringerless System

 



 
 
 
 
 
 
 
Authorised Distributor For: